Product Name: MIHC
- Product Category:
- Product Introduction:
I. General description of MI heating cable
II. Structure of heating cables
III. Product standards
IV. Electrical properties
V. Product data - E-MAIL:
General description of MI heating cable
MI cables are made in special manufacturing process taking a single or several heating alloy as the heating source, electric melting crystal magnesium oxide of high purity and high temperature as the thermal insulator and seamless stainless steel or copper tube as the sheath. PE sheath or that with low smoke and zero halogen can be added in the place exposed in strong corrosion.
● MI heating cables with stainless steel sheath
MI heating cables with stainless steel sheath can be used in the environment of high temperature and great heating power (up to 269W/m). Its maximum temperature resistance can be up to 600℃, the resistance of conductor is within 28000-19.2Ω/km. MI cables are of excellent mechanical strength and corrosion proof.
● MI heating cables with copper sheath
MI heating cables with copper sheath can be used in the environment of high temperature and for long pipe transmission. Its maximum temperature resistance can be up to 250℃, the resistance of conductor is within 480-0.5Ω/km; as for those to be corrosion protected or buried underground, HDPE sheath (MIHC) shall be added, the maximum temperature resistance of MIHC can be up to 90℃; MI cables are of excellent mechanical strength.
● MI heating cables with copper nickel alloy sheath
MI heating cables with copper nickel alloy sheath can be used in the environment of high temperature and for long pipe transmission. Its maximum temperature resistance can be up to 400℃, the resistance of conductor is within 28000-19.2Ω/km; MI cables are of excellent mechanical strength and corrosion proof.
Structure of heating cables
Product standards
Comply with IEC800 (92) Heating Cables with a Rated Voltage of 300/500 V for Comfort Heating and Prevention of Ice Formation for cables with maximum heating temperature less than 250℃ and comply with the enterprise standard for those above 250℃.
Electrical properties
Tolerance of resistance: ±10%
Dielectrical property – withstand voltage of heating cable: 1200VAC/1min
Insulation resistance – test of finished products: 100MΩ/500VDC
Continuity of sheath – the insulation resistance shall be tested after soaking the whole heating cable in water for 12h (including joints), and the value must be 50M/500VDC at least.
Product data
1. MI heating cable with copper core and copper sheath
SN |
Spec. |
Core number |
Voltage class |
Nominal outside diameter |
Core resistance at 20℃ |
Regular length |
Reference weight |
Service temperature |
V |
mm |
Ω/m |
m |
Kg/km |
℃ |
|||
1 |
1M1.1 |
1 |
500 |
7.9 |
0.0011 |
300 |
318 |
< 250 |
2 |
1M1.7 |
1 |
500 |
6.8 |
0.0017 |
350 |
224 |
< 250 |
3 |
1M3 |
1 |
500 |
5.8 |
0.003 |
400 |
153 |
< 250 |
4 |
1M4 |
1 |
500 |
5.2 |
0.004 |
430 |
118 |
< 250 |
5 |
1M7 |
1 |
500 |
4.7 |
0.007 |
460 |
94 |
< 250 |
6 |
1M11 |
1 |
500 |
4.2 |
0.011 |
500 |
72 |
< 250 |
7 |
1M17 |
1 |
500 |
3.9 |
0.017 |
540 |
59 |
< 250 |
8 |
1M23 |
1 |
500 |
3.7 |
0.023 |
600 |
52 |
< 250 |
9 |
1M34 |
1 |
500 |
3.5 |
0.034 |
670 |
46 |
< 250 |
10 |
1M57 |
1 |
500 |
3.4 |
0.057 |
700 |
44 |
< 250 |
2. MI heating cable with Nickel-Chromium alloy core and stainless steel sheath
SN |
Spec. |
Core number |
Voltage class |
Nominal outside diameter |
Core resistance at 20℃ |
Regular length |
Reference weight |
Service temperature |
V |
mm |
Ω/m |
m |
Kg/km |
℃ |
|||
1 |
1M190 |
1 |
500 |
5.8 |
0.190 |
220 |
140 |
< 800 |
2 |
1M280 |
1 |
500 |
5.2 |
0.280 |
280 |
108 |
< 800 |
3 |
1M450 |
1 |
500 |
4.7 |
0.450 |
342 |
86 |
< 800 |
4 |
1M750 |
1 |
500 |
4.2 |
0.750 |
420 |
66 |
< 800 |
5 |
1M1100 |
1 |
500 |
3.9 |
1.100 |
499 |
54 |
< 800 |
6 |
1M1500 |
1 |
500 |
3.7 |
1.500 |
540 |
48 |
< 800 |
7 |
1M2300 |
1 |
500 |
3.5 |
2.300 |
600 |
42 |
< 800 |
8 |
1M4500 |
1 |
500 |
3.3 |
4.500 |
675 |
38 |
< 800 |
9 |
1M7500 |
1 |
500 |
3.2 |
7.500 |
715 |
37 |
< 800 |
10 |
1M11K |
1 |
500 |
3.1 |
11.000 |
760 |
34 |
< 800 |
11 |
2M1100 |
2 |
500 |
6.5 |
1.100 |
180 |
146 |
< 800 |
12 |
2M1500 |
2 |
500 |
6.2 |
1.500 |
195 |
133 |
< 800 |
13 |
2M2300 |
2 |
500 |
5.7 |
2.300 |
234 |
108 |
< 800 |
14 |
2M4500 |
2 |
500 |
5.2 |
4.500 |
280 |
90 |
< 800 |
Certificates
Related Keywords :
MI high temperature industrial heating cable* First Name: | Please fill in your First Name |
* Last Name: | Please fill in your Last Name |
Company name: | Please fill in your company name |
Telephone number: | |
Mobile phone number: | Please fill in your telephone number |
* E-mail: | |
Country: | |
Address: | |
* Inquire intention description: | |
* Validate Code: | |
Please fill in the quantity and description of Inquire products for uniform stocking. | |
Your E-mail: | |
* Content: |
(Up to 1,000 characters) |
Verification code: | Not clear?! |
products center
Heat trace cable
- Low temperature self regulating heating cable
- Middle temperature self regulating heating cable
- High temperature self regulating heating cable
- Pre-assembled heating cable kits
- Parallel resistance constant wattage heating cable
- Series resistance constant wattage heating cable
- Composite sampling analyzer tube
- Mineral insulated heating cable
- Accessories
Underfloor heating
Roof & gutter de-icing
Snow melting
- Constant wattage snow melting heating cable.
- Constant wattage snow melting mat
- Self regulating heating cable
- Accessories
Pre-assembled heating cable kits
Contact Huanrui
E-mail: info@heatcablemat.com
Tel: +86-551-67709531
Fax: +86-551-67709531
Add: Liuzi Road,Feidong Economic Development Zone,Hefei City,Anhui Province,China
- comments in total【Write a Review】Customer Reviews